CHAPTER 4: SETPOINTS
FLEXLOGIC
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–387
FlexElements
There are 8 identical FlexElements™. A FlexElement is a universal comparator, that can be
used to monitor any analog actual value measured or calculated by the relay, or a net
difference of any two analog actual values of the same type. Depending on how the
FlexElement is programmed, the effective operating signal could be either a signed signal
(“Signed” selected for Input Mode), or an absolute value (“Absolute” selected for Input
Mode).
The element can be programmed to respond either to a signal level or to a rate-of-change
(delta) over a pre-defined period of time. The output operand is asserted when the
operating signal is higher than a threshold or lower than a threshold as chosen by the user.
When programming a FlexElement, one must keep in mind the following limitations:
1.
The analog inputs for any FlexElement must be from the same “gender”:
–
current and current (in any combination, phase-symmetrical, phase-phase, kA-A,
differential, restraint, etc.)
–
voltage and voltage (as above)
–
active power and active power (Watts and Watts)
–
reactive power and reactive power (Vars and Vars)
–
apparent power and apparent power (VA and VA)
–
angle and angle (any, no matter what signal, for example angle of voltage and
angle of current are a valid pair)
–
% and % (any, for example THD and harmonic content is a valid pair)
–
V/Hz and V/Hz
–
°C and °C
–
I
2
t and I
2
t
–
FlexElement actual and FlexElement actual
For all the other combinations, the element displays 0.000 or N/A and will not assert
any output operand.
2.
The analog value associated with one FlexElement can be used as an input to another
FlexElement “Cascading”.
Figure 4-158: FlexElement logic diagram
894017$1.CDR
FUNCTION:
SETTING
Enabled = 1
SETTINGS
INPUT COMPARISON
MODE:
OPERATING MODE:
DIRECTION:
PICKUP:
RATE OF CHANGE TIME
UNIT (dt):
RATE OF CHANGE TIME:
RUN
INPUT 1(+):
SETTINGS
Actual Value
FLEXLOGIC OPERANDS
FE 1 OP
FE 1 PKP
INPUT 2 (-):
Actual Value
+
-
FE 1 Op Signal
ACTUAL VALUE
Disabled = 0
BLOCK:
SETTING
Off = 0
AND
t
PKP
t
DPO
SETTINGS
DROPOUT DELAY:
PICKUP DELAY:
HYSTERESIS:
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...