4–298
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
Figure 4-122: Power Factor Conventions
In a synchronous machine, this type of machine can operate in lagging (under excitation),
leading (over excitation) or unity power factor conditions depending on the applied field
current. As shown in below figure, V-curves are normally provided by the machine
manufacturer to determine the relationship between the filed current and power factor.
Figure 4-123: Synchronous Machine Simplified V-Curve Example
Path
:
Setpoints > Monitoring > Functions > Power Factor
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Default: Disabled
This setting enables the Power Factor Trip functionality.
TRIP LEAD LEVEL
Range: 0.05 to 1.00 in steps of 0.01
Default: 1.00 Lag
This setting specifies the Power Factor Lead Trip level.
+P
-P
+Q
-Q
Lag PF=1
Lead PF=-1
Lead PF=-1
Lag PF=1
Trip Lag PF
Trip Lead PF
Normal
Operating Zone
Ö
Ö
Ö
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...