CHAPTER 4: SETPOINTS
PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–195
Sensitive Ground
Instantaneous
Overcurrent
Protection (50SG)
The 889 relay is equipped with Sensitive Ground Instantaneous Overcurrent protection
element. The settings of this function are applied to the measured Sensitive Ground
current for producing Pickup and Trip flags. The Sensitive Ground IOC Pickup flag is
asserted when the Sensitive Ground current is above the PKP value. The Sensitive Ground
IOC Operate flag is asserted if the element stays picked-up for the time defined by the
Sensitive Ground IOC PKP Delay setting. If the Pickup time delay is set to 0.00 seconds, the
Pickup and Operate flags are asserted at the same time. The element drops from Pickup
without operation if the Sensitive Ground current drops below 97 to 98% of the Pickup
value.
Path
:
Setpoints > Protection > Group 1(6) > Current > Sensitive Ground IOC 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
PICKUP
Range: 0.50 to 15.00 A in steps of 0.01 A
Default: 10.00 A
The 50:0.025 Ground input (K1-Ig) range is given above.
In the case of 50:0.025 Ground input (K1-Ig as current input), the pickup level is specified
as Ampere in primary. For example, with a PKP setting of 10.00 A, when the ground
current (primary) is 10.00A, the K1-Ig will measure 10.000 A, and this function should
pick up.
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
This setting defines the operation direction of the Sensitive Ground time overcurrent
element. Entering the direction for the Sensitive Ground IOC element, does not
automatically apply the selection. The direction detection is performed by the element
Sensitive Ground Directional OC, which must be enabled and configured according to
the directionality criteria of the feeder currents.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides the selection for the pickup time delay used to delay the operation
of the protection.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides the selection for the dropout time delay used to delay the dropout
of the detection of the overcurrent condition.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Sensitive Ground IOC is blocked, when the selected operand is asserted.
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...