4–86
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM
CHAPTER 4: SETPOINTS
Breakers
The breaker connection/disconnection to/from the power system (racked-out by the
breaker racking mechanism, or isolated by the associated disconnect switches on a fixed
circuit breaker) is provided by monitoring the contact input “BKR CONNECTED”. If the
contact input selected under the “BKR CONNECTED” setpoint is asserted, the breaker is
considered connected to the primary system. When the breaker is determined
disconnected, the breaker state is shown to be neither open, nor closed.
NAME
Range: Up to 13 alphanumeric characters
Default: BKR1 (BKR2)
CONTACT INPUT 52a
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52a.
CONTACT INPUT 52b
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52b.
CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
Select a contact input to show whether the breaker is connected (Racked-in, or
disconnect switches switched-on), or disconnected (racked-out, or disconnect switches
switched-off) from the system.
TRIP RELAY SELECT
Range: Off, Relay X
Default: Relay 1
For the 889 with two breakers, any output relay from the list of available output relays
can be programmed for breaker tripping action. Please refer to the table from the
section
for more detail on output relay availability with respect to their
assignment.
CLOSE RELAY SELECT
Range: Off, Any Output Relay (889 with two breakers),
Relay 2 to Relay X (889 with one breaker)
Default: Relay 2
Refer to the table from the section
for more detail on output relay
availability with respect to their assignment.
NOTE
NOTE:
For the 889 with one breaker, if "Relay 2" is selected, Auxiliary Relay 2 is not available for
selection in any element.
Table 4-18: Breaker status depending on availability of contacts 52a and 52b
52a Contact Configured
52b Contact Configured
Breaker Status
Open
Closed
Yes
Yes
52a contact open
52b contact closed
52a contact closed
52b contact open
Yes
No
52a contact open
52a contact closed
No
Yes
52b contact closed
52b contact open
No
No
Breaker Not Configured
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...