CHAPTER 5: STATUS
FLEX STATE
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5–9
Flex State
Path
:
Status > Flex States
There are 256 Flex state bits available. The status value indicates the state of the given Flex
state bit.
Communications
GOOSE Rx and Tx
The 889 supports 3 GOOSE transmissions and 8 GOOSE receptions each with 64 items per
transmission or reception. Non-structured GOOSE is supported. Each item within the
GOOSE message can be a digital or analog value. Messages are launched within one scan
of a digital point status change or an analog exceeding its deadband.
The 889 server supports a subset of the server features described in part 7.2 of the
IEC61850 standard.
GOOSE MESSAGING
As indicated above, the 889 supports 3 GOOSE transmissions and eight GOOSE receptions
as shown in the table below:
* Launch speed is measured by comparing the time stamp in SOE of digital remote output
status change to the time stamp of message seen on the network by a computer who’s
clock is synchronized by an IRIG-B card to the same IRIG-B source as the 889 relay.
REMOTE INPUTS
Path:
Status > Communications > Remote Inputs
The present state of the 32 remote inputs are shown here. The state displayed is the
remote point unless the remote device has been established to be “Offline” in which case
the value shown is the programmed default state for the remote input.
GGIO1 INDICATIONS
Path:
Status > Communications > GGIO1 Indications
The present state of the 32 GGIO1 Indications are shown here. There are up to 32 GGIO
indications that can be used to map any FlexLogic operand into the IED 61850 information
model. Default value is Off.
GOOSE STATUS
Path
:
Status > Communications > GOOSE Status
Service
Launch
Speed*
Support for
Programmable
time to live
# of Tx # of Rx
Test Bit
Support
Number of
items in
each
transmissi
on or
reception
Number of
remote
inputs per
relay
Configurab
le GOOSE
Within 2 ms
(1 CPU
scan)*
Time to live
programmable
from 1000 to
60000 ms
3
8
Devices
Y
64 Data
Items per
Data Set
32
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...