CHAPTER 4: SETPOINTS
FLEXLOGIC
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–383
Non-volatile Latches
The purpose of a Non-volatile Latch is to provide a permanent logical flag that is stored
safely and does not reset when the relay reboots after being powered down. Typical
applications include sustaining operator commands or permanently blocking relay
functions such as Autorecloser, until a deliberate HMI action resets the latch.
Operation of the element is summarized in the following table:
Path
:
Settings > FlexLogic > Non-volatile Latches > Latch 1(16)
NV LATCH 1 FUNCTION
Range: Disabled, Enabled
Default: Disabled
The setpoint enables or disables the Non-volatile Latch function.
NV LATCH 1 TYPE
Range: Reset-Dominant, Set-Dominant
Default: Reset-Dominant
The setting characterizes NV LATCH 1 to be set- or reset-dominant.
NV LATCH 1 SET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand ‘SET’ NV LATCH 1.
LATCH 1 RESET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand ‘RESET’ NV LATCH 1.
LATCH 1 TYPE
LATCH 1 SET
LATCH 1 RESET
LATCH 1 ON
LATCH 1 OFF
Reset Dominant
On
Off
On
Off
Off
Off
Previous State
Previous State
On
On
Off
On
Off
Set Dominant
On
Off
On
Off
On
Off
Off
Previous State
Previous State
Off
On
Off
On
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...