889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
Breaker
Trip and Close Circuit
Monitoring
The 889 relay provides Trip and Close Circuit Monitoring elements.
The first and second Form A relay outputs on slot “F” include a circuit to monitor the DC
voltage across the output contact when it is open. To do that, an external jumper is wired
between the terminals “FA_1 COM” and “FA_1 OPT/V” for the Trip coil monitoring, or/and
“FA_2 COM” and “FA_2 OPT/V” for the Close coil monitoring.
The monitor contains a level detector whose output is set to logic 1 (ON) when the voltage
is above 20 volts. The voltage monitor is used to check the health of the overall trip and
closing circuit.
The two figures below show the two different connections of the breaker trip and close
coils to the relay’s trip and close output relays for either no voltage monitoring and for
voltage monitoring of the circuits.
Figure 4-112: Trip Coil Circuit without Monitoring
V
DC +
DC -
Output Relay 1 (TRIP)
52a
contact
Trip
Coil
FA_1
COM
FA_1
NO
FA_1
OPT/V
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...