2–6
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MECHANICAL INSTALLATION
CHAPTER 2: INSTALLATION
Figure 2-8: Depth reducing collar installation
To mount an 8 Series relay with a depth reducing collar, follow these steps:
1.
Drill mounting holes as shown on the panel cutout drawing (
).
2.
Mount the required collar (depth 1.375" or 3") on the captive unit using eight screws as
shown.
3.
Mount the combined unit and collar on the panel using eight screws as shown.
DEPTH REDUCING COLLAR
GE PART# 1009-0311 3IN (76.2MM) DEPTH
GE PART# 1009-0310 1.375IN (34.9MM) DEPTH
8 SERIES UNIT
8-32x3/8IN P/HD PHIL BLK
GE PART# 1408-0306 (qty:16)
Tightening Torque: 15 in lb (1.7 Nm)
892703A1.dwg