889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 4: SETPOINTS
MODBUS SLAVE ADDRESS
Range: 1 to 254 in steps of 1
Default: 254
For the RS485 ports each 889 must have a unique address from 1 to 254. Address 0 is
the broadcast address to which all Modbus slave devices listen. Addresses do not have
to be sequential, but no two devices can have the same address, otherwise conflicts
resulting in errors occur. Generally, each device added to the link uses the next higher
address starting at 1.
MODBUS TCP PORT NUMBER
Range: 1 to 65535 in steps of 1
Default: 502
The TCP port number used with Modbus over Ethernet. Note that the maximum number
of simultaneous Modbus connections supported over Ethernet is:
•
three for an 889 without the communications card,
•
five for an 889 with the communications card.
MODBUS ACTIVITY TIMEOUT
Range: 0 to 3600 s in steps of 1
Default: 0 s
The Modbus Activity Timeout specifies the minimum time without Modbus
communication. This timeout is used to declare the Modbus ‘Loss of Communication’
state.
The Modbus state is always Active if the Modbus Activity Timeout is 0 s.
MODBUS ERROR RESPONSES
The following exception response codes are implemented.
Function Code 03H (Read Setpoints)
Modbus Implementation: Read Holding Registers
889 Implementation: Read Setpoints
For the 889 implementation of Modbus, the function code can be used to read any
setpoints (“holding registers”). Holding registers are 16 bit (two byte) values transmitted
high order byte first. As a result all 889 Setpoints are sent as two bytes. The maximum
number of registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
number of data bytes to follow, the data itself and the CRC. Each data item is sent as a two
byte number with the high order byte sent first.
For example, consider a request for slave 17 to respond with 3 registers starting at address
006B. For this example the register data in these addresses is as follows:
Error ID
Exception
Description
01
ILLEGAL FUNCTION
The function code transmitted is not one of the
functions supported by the 889.
02
ILLEGAL DATA ADDRESS
The address referenced in the data field transmitted
by the master is not an allowable address for the 889.
03
ILLEGAL DATA VALUE
The value referenced in the data field transmitted by
the master is not within range for the selected data
address.
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...