CHAPTER 4: SETPOINTS
PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–197
Figure 4-69: Sensitive Ground Instantaneous Overcurrent Protection logic diagram
894040A2.cdr
SETPOINTS
Sensitive Ground current
(Isg)
RUN
SETPOINTS
BLOCK:
Of
f
= 0
PICKUP:
Isg > PICKUP
OR
AND
Operate Output Relay
1 (TRIP)
LED: TRIP
OR
OR
From Cold Load Pickup
From Sensitive Ground CT
AND
AND
SETPOINT
FUNCTION:
Disabled
= 0
T
rip
Alarm
Latched
Alarm
PICKUP
DELA
Y
:
SETPOINTS
t
PKP
From
Autoreclose
(per shot settings)
LED
: ALARM
RESET
Command
AND
S
R
LA
TCH
LED
: PICKUP
SETPOINTS
Do Not Operate,
Operate
OUTPUT
RELA
YS
3 to 7
DIRECTION:
DROPOUT
DELA
Y
:
t
RST
Configurable
SGnd IOC 1
PKP
FLEXLOGIC OPERANDS
SGnd IOC 1
OP
FLEXLOGIC OPERANDS
Direction (from Sens Ground
Directional OC element
)
Set
Dominant
From Manual Close
Blocking
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...