![GE Multilin 889 Скачать руководство пользователя страница 529](http://html.mh-extra.com/html/ge/multilin-889/multilin-889_instruction-manual_123014529.webp)
CHAPTER 4: SETPOINTS
TESTING
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–399
TEST STATUS
Range: None, Testing, Passed, Failed
Default: None
This value indicates the result of the test.
TESTS RUN
Range: 0 to 65535 in steps of 1
Default: 0
The remaining test iterations once the loop-back test has been initiated.
TESTS PASSED
Range: 0 to 65535 in steps of 1
Default: 0
This actual values indicates how many iterations have passed.
TESTS FAILED
Range: 0 to 65535 in steps of 1
Default: 0
This actual value indicates how many iterations have failed.
NOTE
NOTE:
If the loop-back test is successful the Tests Passed counter will be equal to the Number of
Tests that were specified. In addition, the Test Status can be read to determine the result of
the test.
Steps required to initiate an Ethernet Loopback test
1.
Enable Factory Service Mode
2.
Write the “Number of Tests” register. The default is 500, and there is usually no need to
change it.
3.
Initiate the test by Writing 1 for “Yes” to the “Test Start” command.
4.
Read the “Tests to Run” register. Once it is 0 the test is complete.
5.
Read the “Test Status” register. The values of 0, 1, 2 and 3 are for None, Testing, Passed
and Failed, respectively.
6.
Read the “Tests Passed” count and “Tests Failed” count registers to determine the
number of tests that passed and failed respectively.
Table 4-41: Modbus Addresses
Data Item
Data type
Ethernet Port 4
Modbus Address
Ethernet Port 5
Modbus Address
Number of Tests
Setpoint, 16 bit value
0XF212
0XF218
Test Start (Command)
Setpoint, 16 bit enumeration
0XF213
0XF219
Test Status
Actual Value, 16 bit enumeration
0XF214
0XF21A
Tests to Run
Actual Value, 16 bits
0xF215
0XF21B
Tests Passed (Count)
Actual Value, 16 bits
0xF216
0XF21C
Tests Failed (Count)
Actual Value, 16 bits
0xF217
0XF21D
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...