CHAPTER 4: SETPOINTS
FLEXLOGIC
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–381
The characteristics of the logic gates are tabulated below, and the operators available in
FlexLogic™ are listed in the FlexLogic™ operators table.
Table 4-39: FlexLogic Gate Characteristics
One-shot
POSITIVE ONE SHOT One shot that responds
to a positive going edge.
A ‘one shot’ refers to a
single input gate that
generates a pulse
response to an edge on
the input. The output
from a ‘one shot’ is True
(positive) for only one
pass through the
FlexLogic equation. There
is a maximum of 64 ‘one
shots’.
NEGATIVE ONE
SHOT
One shot that responds
to a negative going
edge.
DUAL ONE SHOT
One shot that responds
to both the positive and
negative going edges.
Logic gate
NOT
Logical NOT
Operates on the previous
parameter.
OR(2)
↓
OR(16)
2 input OR gate
↓
16
input OR gate
Operates on the 2
previous parameters.
↓
Operates on the 16
previous parameters.
AND(2)
↓
AND(16)
2 input AND gate
↓
16
input AND gate
Operates on the 2
previous parameters.
↓
Operates on the 16
previous parameters.
NOR(2)
↓
NOR(16)
2 input NOR gate
↓
16
input NOR gate
Operates on the 2
previous parameters.
↓
Operates on the 16
previous parameters.
NAND(2)
↓
NAND(16) 2 input NAND gate
↓
16
input NAND gate
Operates on the 2
previous parameters.
↓
Operates on the 16
previous parameters.
XOR(2)
2 input Exclusive OR gate Operates on the 2
previous parameters.
LATCH (S,R)
Latch (set, reset): reset-
dominant
The parameter preceding
LATCH(S,R) is the reset
input. The parameter
preceding the reset input
is the set input.
Timer
TIMER 1
↓
TIMER 32 Timer set with
FlexLogic™ timer 1
settings.
↓
Timer set with
FlexLogic™ timer 32
settings.
The timer is started by
the preceding parameter.
The output of the timer is
TIMER #.
Assign virtual output
= Virt Op 1
↓
= Virt
Op 32
Assigns previous
FlexLogic™ operand to
virtual output 1.
↓
Assigns
previous FlexLogic™
operand to virtual output
96.
The virtual output is set
by the preceding
parameter
GATES
NUMBER OF INPUTS
OUTPUT IS ‘1’ (= ON) IF...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
TYPE SYNTAX
DESCRIPTION
NOTES
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...