CHAPTER 3: INTERFACES
SOFTWARE INTERFACE
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
3–23
Configuring Ethernet
Communications
Before starting, verify that the Ethernet cable is properly connected to the RJ-45 Ethernet
port.
FASTPATH:
889 supports a maximum of 3 TCP/IP sessions.
1.
Install and start the latest version of the EnerVista 8 Series Setup software (available
from the GE EnerVista CD or Website). See the previous section for the installation
procedure.
2.
Click on the
Device Setup
button to open the Device Setup window and click the
Add
Site
button to define a new site.
3.
Enter the desired site name in the "Site Name" field. If desired, a short description of
the site can also be entered. In this example, we will use “Substation 1” as the site
name.
4.
The new site appears in the upper-left list.
5.
Click the
Add Device
button to define the new device.
6.
Enter the desired name in the "Device Name" field, and a description (optional).
7.
Select “Ethernet” from the Interface drop-down list. This displays a number of
interface parameters that must be entered for proper Ethernet functionality.
8.
Enter the IP address, slave address, and Modbus port values assigned to the 889 relay
(from the
Setpoints > Device > Communications
menu).
9.
Click the
Read Order Code
button to connect to the 889 and upload the order code. If
a communications error occurs, ensure that the Ethernet communication values
correspond to the relay setting values.
10. Click
OK
when the relay order code has been received. The new device will be added
to the Site List window (or Online window) located in the top left corner of the main
EnerVista 8 Series Setup software window.
The 889 Site Device has now been configured for Ethernet communications. Proceed to
the following section to begin communications.
Connecting to the
Relay
Now that the communications parameters have been properly configured, the user can
easily communicate with the relay.
1.
Expand the Site list by double clicking on the site name or clicking on the «
+
» box to
list the available devices for the given site.
2.
Desired device trees can be expanded by clicking the «
+
» box. The following list of
headers is shown for each device:
Device Definition
Status
Metering
Quick Setup
Setpoints
Records
Maintenance.
3.
Expand the
Setpoints > Device > Front Panel
list item and double click on
Display
Properties
or
Default Screens
to open the settings window as shown:
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...