4–344
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL
CHAPTER 4: SETPOINTS
Figure 4-145: Pushbutton “Tag” logic diagram
FASTPATH:
The pushbuttons, Tag, Block and Bypass Block are used for both breakers and switches
when selected in the SLD. Only one component at the time can be selected in the SLD.
FASTPATH:
Tagging, blocking, or bypassing block can be performed in Local Mode, and only when the
component (breaker or switch) is selected in the SLD. The applied action of tagging,
blocking or bypassing block is retained for this component after it’s been deselected. To
change the status of the applied action, the component need be reselected.
FASTPATH:
The Local Mode control allows programming of separate pair of PBs for Open and Close
commands to breakers and for Open and Close commands to switches. If desired, one pair
of pushbuttons can be programmed for Open and Close commands to both breakers and
switches.
FLEXLOGIC OPERAND
BKR [X] Selected
SW [X] Selected
AND
S
Latch
R
Non-Volatile
Latch
Reset-
Dominant
positive
one shot
Tag
PB “TAG”
AND
FLEXLOGIC OPERAND
Tag ON
FLEXLOGIC OPERAND
Tag OFF
SETTING
TAGGING
Enabled = 1
OR
FLEXLOGIC OPERAND
SBO Enabled
894199A1.cdr
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...