Timer Type
When Timer is selected, the equation will be utilized to obtain a true/false result to activate a time delay. The
equation can then be selected as a timer input on another Logic equation as T1-T20 corresponding to the
number of the math/logic equation 1-20.
The
Tagname
entry allows the user or OEM to assign a specific name for each equation, up to 11 characters
in length. This name will be used throughout the MCTB runtime application to identify the calculated value on
the Overview screen and in the trend and data logging point selection lists. The default tag names are Math1
to Math20. The tagname will also be shown in the Inputs drop-down menus on the equation entry screen for
reference when selecting math or timer equations as inputs to other equations.
The
Trigger
selection is used to determine what condition must be met in order for the equation to be solved.
If the condition is not met, the runtime application will skip the equation and not evaluate it. The default selection
of “Always” means that the equation is constantly evaluated and a new result determined every scan.
Depending upon the configuration of the MCTB, the following additional trigger selections are available:
S1_EventIn
Loop 1 (slot 1) event input. If selected, the equation will be evaluated when the event input is
activated. This selection is available when the event input function of the B42 in slot 1 is
configured for any of the functions except for failure transfer.
S2_EventIn
Loop 2 (slot 2) event input. If selected, the equation will be evaluated when the event input is
activated. This selection is available when the event input function of the B42 in slot 2 is
configured for any of the functions except for failure transfer.
S3_EventIn
Loop 3 (slot 3) event input. If selected, the equation will be evaluated when the event input is
activated. This selection is available when the event input function of the B42 in slot 3 is
configured for any of the functions except for failure transfer.
S1_EvOut2
Loop 1 (slot 1) event output 2. If selected, the equation will be evaluated when the event output
is activated. This selection is available when the output 2 function the B42 in slot 1 is configured
for event, manual event only or math/logic event output only.
S1_EvOut3
Loop 1 (slot 1) event output 3. If selected, the equation will be evaluated when the event output
is activated. This selection is available when the output 3 function the B42 in slot 1 is configured
for event, manual event only or math/logic event output only.
S1_EvOut4
Loop 1 (slot 1) event output 4. If selected, the equation will be evaluated when the event output
is activated. This selection is available when the output 4 function the B42 in slot 1 is configured
for event, manual event only or math/logic event output only.
Содержание MCTB 4.3
Страница 24: ...MCTB 24...
Страница 195: ...MCTB 195...
Страница 227: ...MCTB 227 A 5 SmartIO Monitor Module Specifications...
Страница 228: ...MCTB 228 A 6 Expansion IO Module Specifications...
Страница 229: ...MCTB 229 A 7 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Страница 230: ...MCTB 230...
Страница 231: ...MCTB 231 Open Frame Power Supply Specifications...
Страница 232: ...MCTB 232...
Страница 233: ...MCTB 233 A 8 Power On Delay Relay Specifications GE1A C10HA110...
Страница 234: ...MCTB 234...