The following 20 registers of the automatic program contain the data for step 1 of the program.
Modbus
Address
Register Number
Parameter Description
Data *D
Range
*E
*F
Type
Low
High
Unit
401121
1120
(0x0460)
Step Number
*
W
0
63
-
401122
1121
(0x0461)
Step Type
W
*E5
*E5
-
401123
1122
(0x0462)
Ramp Target Setpoint Loop 1
W
-32768
32767
PV
401124
1123
(0x0463)
Ramp Time or Ramp Rate
W
0
5999
-
401125
1124
(0x0464)
Event Selections 1, 2, 3
W
*E6
*E6
-
401126
1125
(0x0465)
Holdback Type Loop 1
W
*E7
*E7
-
401127
1126
(0x0466)
Dwell Time
W
0
9999
-
401128
1127
(0x0467)
Jump Step
W
0
63
-
401129
1128
(0x0468)
Jump Cycles
W
1
9999
-
401130
1129
(0x0469)
Final Setpoint Loop 1
W
-32768
32767
PV
401131
1130
(0x046A)
Ramp Target Setpoint Loop 2
W
-32768
32767
PV
401132
1131
(0x046B)
Event Selections 4, 5, 6
W
*E8
*E8
-
401133
1132
(0x046C)
Holdback Type Loop 2
W
*E7
*E7
-
401134
1133
(0x046D)
Final Setpoint Loop 2
W
-32768
32767
PV
401135
1134
(0x046E)
Ramp Target Setpoint Loop 3
W
-32768
32767
PV
401136
1135
(0x046F)
Event Selections 7, 8, 9
W
*E9
*E9
-
401137
1136
(0x0470)
Holdback Type Loop 3
W
*E7
*E7
-
401138
1137
(0x0471)
Final Setpoint Loop 3
W
-32768
32767
PV
401139
1138
(0x0472)
Wait Selections
W
*E10
*E10
-
401140
1139
(0x0473)
Wait Setpoint
W
-32768
32767
PV
*
The
Step Number
must be offset by -1 when writing step data to the MCTB. Steps 1-64 will be sent with the
step number as a value of 0-63 (-1 offset).
All remaining steps of the program follow the same format and data structure as is represented for step
one above. Up to the following 1260 registers are used to contain the additional step data of the
program as required for steps 2 through 64. Since few if any programs will contain the maximum of 64
steps, it is only necessary to write the step data for the number steps used in the program.
Modbus Addresses
Register Numbers
401141
– 401160
1140 (0x0474)
– 1159 (0x0487)
Program Step 2 Data Registers
401161
– 401180
1160 (0x0488)
– 1179 (0x049B)
Program Step 3 Data Registers
401181
– 401200
1180 (0x049C)
– 1199 (0x04AF)
Program Step 4 Data Registers
401201
– 401220
1200 (0x04B0)
– 1219 (0x04C3)
Program Step 5 Data Registers
401222
– 401240
1220 (0x04C4)
– 1239 (0x04D7)
Program Step 6 Data Registers
401241
– 401260
1240 (0x04D8)
– 1259 (0x04EB)
Program Step 7 Data Registers
401261
– 401280
1260 (0x04EC)
– 1279 (0x04FF)
Program Step 8 Data Registers
401281
– 401300
1280 (0x0500)
– 1299 (0x0513)
Program Step 9 Data Registers
---------------------------------------------------------------------------------------------------------------------------------
through
---------------------------------------------------------------------------------------------------------------------------------
402381 - 402400
2380 (0x094C)
– 2399 (0x095F)
Program Step 64 Data Registers
Содержание MCTB 4.3
Страница 24: ...MCTB 24...
Страница 195: ...MCTB 195...
Страница 227: ...MCTB 227 A 5 SmartIO Monitor Module Specifications...
Страница 228: ...MCTB 228 A 6 Expansion IO Module Specifications...
Страница 229: ...MCTB 229 A 7 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Страница 230: ...MCTB 230...
Страница 231: ...MCTB 231 Open Frame Power Supply Specifications...
Страница 232: ...MCTB 232...
Страница 233: ...MCTB 233 A 8 Power On Delay Relay Specifications GE1A C10HA110...
Страница 234: ...MCTB 234...