7.3 Troubleshooting
When the protective function is activated:
(1) Overcurrent (AOC)
Perform wiring correctly.
Is the phase order of wiring at L1/R, L2/S, L3/T, R1, S1
and T1 correct?
Reduce the load or
select a converter
having a larger capacity.
Connect the converter
to the suitable power
supply.
Is the load too large?
Does the source voltage exceed the specification?
Overcurrent
AOC
Failure of the converter is probable.
Contact FUJI.
NO
NO
NO
NO
YES
YES
Remove the short circuit
or grounding fault.
Is there a short circuit or grounding fault in wiring or
devices in the AC or DC circuit?
YES
YES
(2) Overvoltage (AOV, dOV)
Reduce the source
voltage to within the
upper limit.
Is the source voltage within the specification range?
Is there a power failure during regeneration operation?
Is the regeneration load too large?
Is the function activated at the end of quick acceleration?
Is the function activated when the load is quickly reduced?
Is a generator used for AC power supply?
Set a longer
acceleration time to the
inverter.
Internal converter
adjustment is required.
Overvoltage
AOV,dOV
The braking system must be
examined. Contact FUJI.
Contact FUJI.
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
Perform wiring correctly.
Is the phase order of wiring at L1/R, L2/S, L3/T, R1, S1
and T1 correct?
NO
· Set a longer deceleration
time to the inverter.
· Examine the regeneration
load.
· Examine the converter
capacity.
7-4