3 Installation and Connection
3.1 Operating Environment
Install the converter in an environment shown in Table 3.1-1.
Table 3.1-1 Environmental Requirements
Item
Specifications
Site location
Indoors
Ambient temperature
-10 to +40°C
Relative humidity
5 to 95% (No condensation)
Atmosphere
The converter must not be exposed to dust, direct sunlight, corrosive gases, flammable gases,
oil mist, vapor or water drops.
The atmosphere can contain a small amount of salt.
The converter must not be subjected to sudden changes in temperature that will cause
condensation to form.
Altitude
1000 m max.
(Refer to Table 3.1-2 for altitudes exceeding 1000 m.)
Vibration
2 to 9 Hz:
0.3 mm (Max. amplitude)
9 to 200 Hz: Less than 1 m/s
2
(0.1 G)
Table 3.1-2 Output Current Derating Factor in Relation to Altitude
Altitude
Output current derating factor
1000 m or lower
1.00
1000 to 1500 m
0.97
1500 to 2000 m
0.95
2000 to 2500 m
0.91
2500 to 3000 m
0.88