The new data of the function code is not reflected on converter operation until the FUNC/DATA key is pressed to
save it; there is no change in the action while the data is changed with
Λ and V keys. The data may not be changed if
the data is protected or data change is prohibited during operation. The reason why the data is not changed includes
the following.
Display
Cause of prohibition of change
Resetting method
DATA PRTCTD
Data is protected with function code F00.
Change function code F00 to "0."
CNV RUNNING
A function code that cannot be changed during operation
of the converter is being changed.
Stop converter operation.
Example of data
change 3
∧
F04
LED MNTR
0:PWR %
0
~
5
F04
LED MNTR
0:PWR %
1:PWR kW
0
~
5
∧
F04
LED MNTR
0:PWR %
2:INPUT I
0
~
5
∧
F04
LED MNTR
0:PWR %
5:FREQ
0
~
5
∨
×n
F04
LED MNTR
0:PWR %
4:DC LNKV
0
~
5
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
E15 RHC-OL-WAR
E16
FAN STOP
E17
I-LIM HYS
E18
AO1 FUNC
≫
≫
∧
∨
≫
×3
E14
I/O OP/CL
OP
CL
RUN X1 Y1 2 3 5 30
≫
F/D
The blinking cursor moves
among active options only.
Press the F/D key to
validate data entry.
Λ
or
V
key: movement in one
direction only
×2
• Example of data change 4 is for I/O
function setting (normally
open/closed).
The function code cannot be
changed during operation.
Example of data
change 4
5-8