12.1.2 Compliance with EMC standards
The CE marking on inverters does not ensure that the entire equipment including our CE-marked products is
compliant with the EMC Directive. Therefore, CE marking for the equipment shall be the responsibility of the
equipment manufacturer. For this reason, Fuji’s CE mark is indicated under the condition that the product shall be
used within equipment meeting all requirements for the relevant Directives. Instrumentation of such equipment shall
be the responsibility of the equipment manufacturer.
Generally, machinery or equipment includes not only our products but other devices as well. Manufacturers,
therefore, shall design the whole system to be compliant with the relevant Directives.
List of EMC-compliant filters
To satisfy the requirements noted above, use inverters in combination with an external filter (option) dedicated to
Fuji inverters. In either case, mount inverters in accordance with the installation procedure given below. To ensure
the compliance, it is recommended that inverters be mounted in a metal panel.
Power
supply
voltage
PWM converter
MD/LD
mode
Filter
Remarks
type
Leakage current *1
Under
normal
conditions
Under
worst-case
conditions
RHC
Three-phase
690V
RHC132S-69DE
MD
/LD
FN3359HV-250-28
57
339
RHC160S-69DE
RHC200S-69DE
RHC250S-69DE
FN3359HV-400-99
57
339
RHC280S-69DE
RHC315S-69DE
RHC355S-69DE
RHC400S-69DE
FN3359HV-600-99
57
339
RHC450S-69DE
*1 Calculated based on these measuring conditions: 690V, 50 Hz, interphase voltage unbalance ratio 2%.
Recommended installation procedure
To make the machinery or equipment fully compliant with the EMC Directive, have certified technicians wire the
filter stack, the PWM converter, the diode rectifier, the inverter and the motor and in strict accordance with the
procedure described below.
When an EMC-compliant filter (option) is externally used
1) Mount the filter stack, the PWM converter, the diode rectifier, the inverter and the filter on a grounded panel or metal plate. Use
shielded wires for the motor cable and route the cable as short as possible. Firmly clamp the shields to the metal plate to ground
them. Further, connect the shielding layers electrically to the grounding terminal of the motor.
2) For connection to control terminals of the filter stack, the PWM converter, the diode rectifier and the inverter and for connection of
the RS-485 communication signal cable, use shielded wires. As with the motor, clamp the shields firmly to a grounded panel.
SVG1S series
U
V
W
G G
�
� �
G
RHF-D series
L1
L2
L3
U
0
V0
W
0
G G
RHC-D series
L1/R
L2/S
L3/T
P(+)
N(-)
G G
P(+)
N(-)
Power
Supply
Three –
phase
MCCB
or
RCD/ELCB*
EMC -
compliant
filter
(optional)
Metal panel
Shielded
cable
Motor
Note :
Connect the shielding layer of
shielded cable to the motor and
panel electrically and ground the
motor and panel.
* With overcurrent protection
In the case of the combination of the PWM converter with RHF and the inverter.
Figure 12.1-1 Mounting an EMC-compliant Filter (option) in a Metal Panel
12-2