Transmission baud rate setting switch RSW3
Before turning on the converter, specify the transmission baud rate in the range from "0" to "4."
1
2 3 4
5
7
9
8
6
0
RSW3
B.RATE
Baud rate specifications
No.
Baud rate
0
156 Kbps (Initial value)
1
625 Kbps
2
2.5 Mbps
3
5 Mbps
4
10 Mbps
5 to 9
Setting error (The L.ERR LED lights up.)
Operation state display LED
The link state of CC-Link can be checked at four LEDs.
Specifications of operation state display LED
State
Operation
L.RUN
L.ERR
SD
RD
Correct communication
Correct communication with frequent CRC error due to noise
Failure to respond due to CRC error of received data
No data destined to own station
CRC error in refresh reception in spite of response to polling
CRC error in data destined to own station
○
No data destined to own station or failure to receive data due to noise
Illegal baud rate or station address setting
(0.8s period)
Baud rate or station address setting changed in the middle
Before link start
Failure to receive data due to broken wire or the like, shutdown,
hardware reset, occurrence of Er3, failure in power unit
: Lit,
, Unlit,
: Blink (The LED may erroneously seem to be lit at some transmission speeds.)
Note 1:
If the LEDs are lit in a pattern other than those listed above, a hardware error is probable. Contact us.
Software specifications
Item
Specifications
Op
er
a
tio
n
Operation command
Operation command, alarm reset command, X1 command
Operation state output
Running, power running, regeneration, bit data such as batch alarm signal
Option function codes
H02, H03, H11 (fixed at "0"): Factory shipment setting is "0."
Protective functions
Er4: Network error
* Minor failure: Communication line error (Use function codes H02 and H03 to control
Er4.)
* Serious failure: Option error (The stopping method can be selected with function
codes H02 and H03.)
* Minor failure: If noise is not frequent, the Er4 alarm can be controlled with function codes H02 and H03 to continue
operation.
* Serious failure: Failure such as hardware failure.
9-26
Содержание RHC-D 690V Series
Страница 8: ...Location of General Precaution and Warning Labels PWM Converter RHC D Series vi...
Страница 153: ...10 3 External Dimensions Rank 3 Converter stack RHC132S 69DE RHC160S 69DE RHC200S 69DE 10 4...
Страница 154: ...Rank 4 Converter stack RHC250S 69DE RHC280S 69DE RHC315S 69DE RHC355S 69DE RHC400S 69DE RHC450S 69DE 10 5...