MD mode
LD mode
80
100
120
140
160
180
0
60
120
180
240
300
360
420
480
→
Action time
(s
)
→
Converter input current (%)
(100%: Rated converter input current)
80
100
120
140
0
60
120
180
240
300
360
420
480
→
Action time
(s
)
→
Converter input current (%)
(100%: Rated converter input current)
Figure 7.1-1 Overload Trip Time
RHC
S-69DE
132
160
200
250
280
315
355
400
450
Rated input
current (A)
MD mode
135
163
205
253
283
319
359
405
455
LD mode
163
205
223
283
319
359
45
455
-
7.2 Error Reset
To reset a tripped converter, remove the cause and then press the
RESET
key on the keypad or enter a reset
command
RST
from the control input terminal.
Before turning the reset signal ON, be sure to turn a run command OFF. Otherwise, the converter restarts running
after reset. It is dangerous.