F06 LCD monitor (Language selection)
F06 selects the language to display on the LCD
monitor.
Setting data
Language
0
Japanese
1
English
2
Chinese
F07 LCD monitor (Contrast adjustment)
F59 adjusts the contrast of the LCD monitor. Increasing
the setting data increases the contrast and decreasing it
decreases the contrast
Setting data
0, 1 , 2,
・・・・・
, 8, 9, 10
Contrast
Low High
F08 Carrier frequency
The carrier frequency is fixed at 5 kHz even if any
value is set to F08. When the OPC-VG7-SIR is
mounted, it is fixed at 2.5 kHz.
E codes (Extension terminal functions)
E01 Terminal [X1] function
E01 defines the function of digital input terminal X1.
Setting data
Function
Symbol
0
Enable external alarm trip
THR
1
Cancel current limiters
LMT-CCL
2
73 answerback
73ANS
3
Switch current limiter values
I-LIM
4
Option DI
OPT-DI
Setting procedure
• Select the desired function. Take "73 Answerback" for
example.
• To assign the "73 answerback" function to [X1], set
E01 to "2" (
73ANS
).
• Turn the terminal [X1] (
73ANS
) ON from an external
device to supply a 73 answerback signal.
• Check if the ON/OFF status of
[X1] is acknowledged, on the I/O
check screen of the keypad.
Turning [X1] ON changes
X1
to
X1 in the figure shown at the
right.
• When the terminal is accessed via
the communications link, use the
same screen for checking.
< Configuring contacts as a "normally open" or
"normally closed" contact" >
Contacts can be configured as a "normally open" or
"normally closed" contact, with Function code E14 (I/O
function (Normally open/closed)). For details, refer to
the description of E14.
Function code data = 0
Enable external alarm trip -- THR
Upon receipt of
THR
, the converter trips with alarm
0h2
. This signal is internally held, so an input of
RST
resets the tripped state. Use this signal to stop the
converter because of a failure of an external device.
The factory default is a "normally open" contact. To use
it as a "normally closed" contact, use Function code
E14 to change the setting.
Function code data = 1
Cancel current limiters -- LMT-CCL
This digital input signal cancels the current limiters
defined by H15 through H18. Upon receipt of
LMT-CCL
, the converter disables all those current
limiters.
□
RUN
□
Y1
□
Y5A
□
RST
□
Y2
■
X1
□
Y3
AO1 =
±
xx.xV
0
6-4