Format [32]: Run command, Format [33]: Y1 to Y18
This format is for S01 and M15.
15
8 7
0
[32]
[33]
0) RUN (Run command)
Y1
1) X1
Y2
2) Not used.
Y3
3) Not used.
Not used.
4) Not used.
Y5A
5) Not used.
Not used.
6) Not used.
Not used.
7) Not used.
Not used.
8) Not used.
Y11
9) Not used.
Y12
10) Not used.
Y13
11) X11
Y14
12) X12
Y15
13) X13
Y16
14) X14
Y17
15) RST (Reset command)
Y18
Format [34]: Communications error code
15
8 7
0
M26 code
*
1
Indication on
keypad
*
2
Communications error name
Concrete operation specifications
0
-
Not a communications error
Normal communication
Arbitrary data is written at function code with missing address.
(Those having an excessive address are separately defined.)
Data is read from missing address of the function code.
(
→
Reading "0000")
Data exceeding the allowable range of the S area is written. The data
is limited at the upper or lower limit value.
1 to 31
*
3
-
Characteristic alarm code
exclusively for RHC-D-Type
Alarm code for other than communication characteristic to RHC-D
48 to 70
-
Reserved.
Not used with RHC-D.
71
04
Checksum error, CRC error
Software error
The sum or CRC value does not agree.
72
05
Parity error
Hardware error
*
4
The parity does not agree.
73
06
Others (Overrun, framing, etc.)
Physical (reception) error other than above
74
01
Format error
There is an error in the format. The transmission request character is
incorrect. The end of text character is not transmitted in the designated
order.
75
01
Command error
A code other than the designated command is sent.
76
07
Link priority error
Not used with RHC-D.
77
07
Function code data writing right
error
Not used with RHC-D.
78
02
Function code error
Data exceeding the function code address range is accessed (access
to F09 or later).
Data longer than 16 words is written.
79
07
Write protection
A read-only code (except S codes) is written.
80
03
Data error
Not used.
81
07
Error in writing cycle
Not used.
*1 Communications error codes 71 to 81 are common among models. However, the cause of operation may be characteristic to specific
models.
*2 The keypad does not display the communications error code value itself but displays "panel indication at keypad."
*3 Alarm codes 1 to 31 are the code system characteristic to RHC-D different from inverter assignment.
*4 The parity error is displayed as "other physical errors" (M26: 73) in the RS-485 communication mode.