Function
code
Communications
address
Function code name
Data setting range
Format
485 No Link No.
E16
110h
5Dh
Cooling fan ON/OFF
control
0 or 1
0: Disable
1: Enable
This control detects the temperature of the heat sink
in the converter and turns the cooling fan on or off
automatically. If "Disable" is selected, the cooling
fan keeps running.
42
E17
111h
5Eh
Current limiting signal
(Hysteresis width)
0 to 30%
0
E18
112h
5Fh
AO1 function selection
0 to 10
0: Input power
PWR
1: Input current (rms)
I-AC
2: Input voltage (rm)
V-AC
3: DC link bus voltage
V-DC
4: Source frequency
FREQ
5: +10V output test
P10
6: -10V output test
N10
50
E19
113h
60h
AO4 function selection
(AIO option)
Refer to AO1 function selection.
50
E20
114h
61h
AO5 function selection
(AIO option)
Refer to AO1 function selection.
50
E21
115h
62h
AO1 gain setting
-100.00 to 100.00 (times)
7
E22
116h
63h
AO4 gain setting
(AIO option)
-100.00 to 100.00 (times)
7
E23
117h
64h
AO5 gain setting
(AIO option)
-100.00 to 100.00 (times)
7
E24
118h
65h
AO1 bias setting
-100.0 to 100.0%
6
E25
119h
66h
AO4 bias setting
(AIO option)
-100.0 to 100.0%
6
E26
11Ah
67h
AO5 bias setting
(AIO option)
-100.0 to 100.0%
6
E27
11Bh
68h
AO1-5 filter setting
0.000 to 0.500 s
4
11-4