Conformity to the Low Voltage Directive in the EU (Continued)
3. When used with the inverter, a molded case circuit breaker (MCCB), residual-current-operated protective device
(RCD)/earth leakage circuit breaker (ELCB) or magnetic contactor (MC) should conform to the EN or IEC standards.
4. When you use a residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) for
protection from electric shock in direct or indirect contact power lines or nodes, be sure to install type B of
RCD/ELCB on the input (primary) of the inverter if the power supply is three-phase 690 V.
5. The inverter should be used in an environment that does not exceed Pollution Degree 2 requirements. If the
environment conforms to Pollution Degree 3 or 4, install the inverter in an enclosure of IP54 or higher.
6. Install the inverter, AC or DC reactor, input or output filter in an enclosure with minimum degree of protection of
IP2X (Top surface of enclosure shall be minimum IP4X when it can be easily accessed), to prevent human body from
touching directly to live parts of these equipment.
7. Do not connect any copper wire directly to grounding terminals. Use crimp terminals with tin or equivalent plating to
connect them.
8. When you use an inverter at an altitude of more than 2000 m, you should apply basic insulation for the control circuits
of the inverter. The inverter cannot be used at altitudes of more than 3000 m.
9. Use wires listed in IEC60364-5-52.
RHC□S-69D series
P
o
w
er
s
u
p
pl
y
v
o
lt
ag
e
PWM converter
type
HD/
L
D m
o
d
e
MCCB or
RCD/ELC
B *1
Rated
current(A)
Recommended wire/copper bar size (mm
2
)
Main circuit
Con-
trol
circuit
R0,T0
R1,S1,T1
R3,T3
73A,73C
Main power
input *2
[L1/R, L2/S, L3/T]
PWM converter
output
[P(+),N(-)]
*2,*3
Ground
terminal
[ G]
Charging
circuit
[L4,L5,L6]
Copper
bar
Wire
Copper
bar
Wire
T
h
re
e p
h
as
e 6
9
0
V
RHC132S-69DE
MD
175
t5x30
(150)
70
t4x40
(160)
70
35
2.5
0.75
2.5
LD
200
70
70
35
RHC160S-69DE
MD
200
70
70
35
LD
250
95
120
50
RHC200S-69DE
MD
250
95
120
50
LD
300
120
120
70
RHC250S-69DE
MD
300
t10x30
(300)
150
t8x50
(400)
150
95
LD
350
185
185
95
RHC280S-69DE
MD
350
185
185
95
LD
400
240
240
120
RHC315S-69DE
MD
400
240
240
120
LD
500
240
300
120
RHC355S-69DE
MD
500
240
300
120
LD
500
300
300
150
RHC400S-69DE
MD
500
300
300
150
LD
600
150x2
150x2
150
RHC450S-69DE
MD
600
150x2
150x2
150
12-5