Operating Manual RTM X42.CC Control Center, RTM Monitoring & Control Software
19.03.2019
62
11.3
Alarm messages, warnings
You can activate or deactivate alarm messages or the display of alarm messages in a
dialogue box in the recipe manager.
Additionally, the alarm messages can be forwarded to the PLC, e.g., via relay outputs on
the RTM reception module
Refer to p. 23
Figure 51: Dialogue window alarm message, alarm
Figure 52: alarm off, alarm on, alarm mute
If you have activated relay outputs, these are switched pursuant to the corresponding
settings. If you have also simultaneously activated the display of a dialogue window, it
will appear at the same time as the relay is switched.
Alarm off
No alarm has been configured.
Alarm on
The conditions for at least one alarm message have been activated. At least one relay is
switched. The system status changes...
Alarm mute
If the warning dialogue window does not appear permanently during the solution of the
issue, you have the option to mute the alarm. For this purpose, click on the control
“alarm on”. The display then switches to “alarm Mute”.
The relay drops when you switch to mute, even if the alarm condition is still pending.
If a further error occurs in the meantime, it will not be displayed again as an “alarm on”.
The “alarm Mute” display remains active until all conditions for a warning / alarm event
are removed. Only then does a new alarm event trigger the "alarm on" display again.
alarm events must be “"acknowledged"”. i.e. As soon as “alarm on” is displayed, you
need to press the icon to “Acknowledge”.