Operating Manual RTM X42.CC Control Center, RTM Monitoring & Control Software
19.03.2019
24
Basic setting — Force sensor and relay
Column Description
Gain
Free input of the gain or automatic calculation
refer to Calibration p. 25f
Min. 0.001
Max. 20
Bar display filter
This filter only affects the bar display in the home screen
Bar display
threshold frequency
or number of
measured values
Threshold frequency:
Min. 0.01, Max. 10, Standard 1Hz
Samples:
Min. 2, Max. 5000, Standard 2
Histogram filter
This filter only affects the display of the histogram in the
home screen
Histogram
threshold frequency
or samples
Threshold frequency:
Min. 0.01, Max. 10, Standard 1Hz
Samples:
Min. 2, Max. 5000, Standard 2
Filter Wire Break
This filter affects the response behaviour of the wire break
detection.
Wire break
threshold frequency
Threshold frequency:
Min. 0.01, Max. 10, Standard 1Hz
Wire break
threshold
Threshold for the detection of a wire break. As soon as this
value is undershot and remains undershot for the duration
of the delay time, the "wire break" alarm is issued.
Wire break delay
time
Specifies the time interval by which the threshold must be
undershot to trigger an alarm.
Control Cut-off
Frequency /
Samples
Threshold frequency:
Min. 0.01, Max. 10, Standard 1Hz
Samples:
Min. 2, Max. 5000, Standard 2
Filter control unit
This filter only affects the bar graph display in the home
screen
Table 7: Basic setting - Force sensor and relay