Malfunctions
95
Error
channel
Meaning
Remedy
Activation
parameter
m = module
number 0
Error number 24, error with the parameterisation of the lower limit value
Em.2
An error has
occurred in the
setting of the
lower limit value
pressure P2
parameter
–
Check the parameterisation and carry out the
parameterisation again with correct parame-
ters.
Pm.0.7:
Monitoring of
parameters
Error number 25, error with the parameterisation of the upper limit value;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed. The parameter values entered will be ignored. The
module operates internally with the last valid parameter values.
Em.0
An error has
occurred in the
setting of the
upper limit
value flow rate
parameter
–
Check the parameterisation and carry out the
parameterisation again with correct parame-
ters.
Pm.0.7:
Monitoring of
parameters
Em.2
An error has
occurred in the
setting of the
upper limit
value pressure
parameter
Em.3
An error has
occurred in the
setting of the
upper limit
value pressure
change param-
eter