Malfunctions
Error
channel
Meaning
Remedy
Activation
parameter
m = module
number 0
Error number 26, actuator power supply undervoltage;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed.
Am.0
Undervoltage in
load voltage
supply 24 V DC
–
Check the load voltage supply 24 V DC and
increase if necessary.
–
Check the load voltage supply wiring and
repair if necessary.
Pm.0.2:
Monitoring
U
OUT/A
Error number 29, error in parameterisation;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed. The parameter values entered will be ignored. The
module operates internally with the last valid parameter values.
Em.0
Error in setting
the parameter:
–
Unit flow rate
–
Flow standard
–
Check the parameterisation and carry out the
parameterisation again with correct parame-
ters.
Pm.0.7:
Monitoring of
parameters
Em.1
An error has
occurred in the
setting of the
unit consump-
tion parameter
Em.2
An error has
occurred in the
setting of the
unit pressure
parameter
Em.3
An error has
occurred in the
setting of the
pressure change
sample time
parameter
Em.5
An error has
occurred in the
setting of the
monitor limit
values param-
eter startup