Festo — MSE6-C2M — 2022-08b
Parameterisation
Module parameter: Q_low-Timer reset selection
1 0
2 = DI1
Electrical input 1
1 1
3 = Am.0.2 OR DI0
Logical OR signal:
Output Am.0.2
OR
Electrical input 0
Logic 1, if Am.0.2 = 1 or electrical input
0 = 1
Tab. 72: Q_low-Timer reset selection module parameter
Module parameter: setpoint pressure power-on
Function number
4828 + m * 64 + 28
m = module number 0
Description
The parameter is used to define the setpoint pressure when the supply voltage
is switched on, power-on, if the module is in the user-controlled pressure regu-
lation and blocking function.
Bit
Bit 2
Values
0 = 10 bar, default
1000 kPa; 1450 psi/10
1 = 6 bar
600 kPa; 870 psi/10
Comment
The parameter value is permanently stored in the module and is the valid value
for the next power-on. A change in the parameter value is effective immediately
and can be used in the user-controlled pressure regulation and blocking func-
tion to set a fixed setpoint pressure value.
Tab. 73: Setpoint pressure power-on module parameter
Module parameter: output DO0 selection
Function number
4828 + m * 64 + 28
m = module number 0
Description
The parameter defines the signal to be output at electrical output 0.
Bit
Bit 3
Values
0: DO0 = Am.0.6, default
Signal source for the electrical output
0 is the output value Am.0.6
1: DO0 = VC_PULSE
Signal source for the electrical output
0 is the measuring pulse signal of
the continuous consumption measure-
ment VC
Tab. 74: Output DO0 selection module parameter