Festo — MSE6-C2M — 2022-08b
Functions
The figures show the behaviour of the status LED P2 and the input signal Monitoring of lower critical
limit pressure P2 for the two parameterisation cases:
–
Case 1: lower pressure limit value P2
>
auto standby pressure setpoint value - 0.05 MPa (- 0.5 bar;
- 7.25 psi).
–
Case 2: lower pressure limit value P2
<
auto standby pressure setpoint value - 0.05 MPa (- 0.5 bar;
- 7.25 psi).
Em.2:
pressure P2
Pm.25-26:
lower critical limit pressure P2
Status LED P2
LED P2 not
illuminated
t
LED P2 illuminated
1
Em.3.6:
monitoring of
lower critical limit pressure
P2
0
Pm.23-24 – 0.5 bar:
pressure setpoint auto standby
– 0.5 bar
LED P2 flashes
Fig. 7: Monitoring of lower pressure limit value P2 and status indicator, case 1
Em.2:
pressure P2
Pm.25-26:
lower critical limit pressure P2
Status LED P2
LED P2 not
illuminated
t
LED P2 illuminated
1
Em.3.6:
monitoring of
lower critical limit pressure P2
0
Pm.23-24 – 0.5 bar:
pressure setpoint
auto standby – 0.5 bar
Fig. 8: Monitoring of lower pressure limit value P2 and status indicator, case 2