Functions
33
–
2 = electronic pressure regulation not active
–
3 = user-controlled target pressure = target pressure user variable (Am.2)
Data bit B5 has the following values:
–
0 = automatic pressure control function and blocking function not active, default
–
1 = automatic pressure regulation and blocking function active
The control signal can be used for user controlled or permanent activation of the automatic pressure
control function and blocking function.
Output data, electrical outputs
Data bit B6 has the following values:
–
0 = electrical output 0 sends logic 0, default
–
1 = electrical output 0 sends logic 1
Data bit B7 has the following values:
–
0 = electrical output 1 sends logic 0, default
–
1 = electrical output 1 sends logic 1
Consumption measurement output data
Data bits B12 and B14 have the following values:
–
0 = measurement not active: measurement is stopped, default
–
1 = measurement active: measurement is started or continued
Data bits B13 and B15 have the following values:
–
0 = reset function not active, default
–
1 = reset function active: measured consumption value is reset to value 0
5.2.2.2
Output word Am.1 input address
The output word Am .1 belongs to the selectable input data function and is described in the chapter of
the same name.