5. Diagnosis
5-10
Festo P.BE-DLP-VSE-... en 0206a
Structure of station status 2
Bit
Meaning
Explanation for log. “1”
0
Diag.Prm_Req
The master must configure the Local control unit again
1
—
reserved
2
—
reserved
3
Diag.WD_On
Response monitoring (watchdog) is active
4
Diag.Freeze_Mode
FREEZE activated
5
Diag.Sync_Mode
SYNC activated
6
—
reserved
7
Diag.Deactivated
always log. “0” (set by the Local control unit)
Fig. 5/10: Octet 2 Station status_2 (diagnostic byte 1)
Structure of station status 3
Bit
Meaning
Explanation for log. “1”
0 ... 6
—
reserved
7
Diag.Ext_
Diag_Overflow
always log. “0” (set by the Local control unit)
Fig. 5/11: Octet 3 Station status_3