5. Diagnosis
5-9
Festo P.BE-DLP-VSE-... en 0206a
Structure of station status 1
Bit
Meaning
Explanation for log. “1”
0
Diag.Station_
Non_Existent
Local control unit is no longer/not yet addressable.
Possible causes
– Operating voltage not applied
– Data cable interrupted
– Fault in data cable
1
Diag.Station_Not_Ready
Local control unit for data exchange not yet ready
2
Diag.Cfg_Fault
The configuration data received from the master do not corre-
spond to those ascertained by the Local control unit.
3
Diag.Ext_Diag
Device-related diagnosis exists
Possible causes
– Cable fracture at input/output
– Short circuit/overload at electric outputs
– V
valves <
20.4 V
– V
outputs <
10 V
– V
sensor <
10 V
4
Diag.Not_Supported
log. “1”: The Local control unit does not support the function
requested
5
Diag.Invalid_
Slave_Response
always log. “0” (set by the Local control unit)
log. “1”: The DP master cannot interpret the reply
6
Diag.Prm_Fault
Last parametrizing telegram faulty
log. “1”: Planned type is not correct
7
Diag.Master_Lock
always log. “0” (set by the Local control unit)
log. “1”: Access by a different master
Fig. 5/9: Octet 1 Station status_1 (diagnostic byte 0)
Содержание DLP-VSE Series
Страница 1: ...Manual Local control unit DLP VSE DLP VSE DP DLP VSE ASI Manual 396 535 en 0206a...
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE DLP VSE en 0206a...
Страница 8: ...Contents and general instructions VI Festo P BE DLP VSE en 0206a...
Страница 20: ...1 Summary of components 1 8 Festo P BE DLP VSE en 0206a...
Страница 54: ...3 Installation 3 30 Festo P BE DLP VSE en 0206a...
Страница 84: ...4 Commissioning 4 30 Festo P BE DLP VSE en 0206a...
Страница 104: ...5 Diagnosis 5 20 Festo P BE DLP VSE en 0206a...
Страница 108: ...A Technical specifications and index A 4 Festo P BE DLP VSE en 0206a...