5. Diagnosis
5-5
Festo P.BE-DLP-VSE-... en 0206a
Display
BUS-LED
Operating status
Error treatment
out
normal, no fault
–
lights up red
Hardware fault
S
servicing required
flashes slowly
(1 second inter-
vals)
Field bus connection not correct.
Possible causes
– Station number not correct (e.g. ad-
dress assigned twice)
– switched-off or defective field bus
module
– interrupted, short-circuited or
faulty field bus connection
– Configuration faulty. Master con-
figuration setting in the switch
module
Check the ...
S
address setting
S
field bus module
S
field bus connection
S
configuration of the master and the
setting in the switch module
flashes (out
briefly)
Switch module missing
Switch module defective
S
Insert switch module
S
Replace switch module
Fig. 5/6: Error diagnosis with the red BUS-LED
5.2.2 Diagnosis with PROFIBUS-DP
The Local control unit supports diagnostic possibilities via the
PROFIBUS in accordance with EN 50170 (DIN 19245). (The
device-specific diagnosis is supported).
Please note
The identifier-related or channel-related diagnosis listed in
EN 50170 (DIN 19245) is not supported.
Содержание DLP-VSE Series
Страница 1: ...Manual Local control unit DLP VSE DLP VSE DP DLP VSE ASI Manual 396 535 en 0206a...
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE DLP VSE en 0206a...
Страница 8: ...Contents and general instructions VI Festo P BE DLP VSE en 0206a...
Страница 20: ...1 Summary of components 1 8 Festo P BE DLP VSE en 0206a...
Страница 54: ...3 Installation 3 30 Festo P BE DLP VSE en 0206a...
Страница 84: ...4 Commissioning 4 30 Festo P BE DLP VSE en 0206a...
Страница 104: ...5 Diagnosis 5 20 Festo P BE DLP VSE en 0206a...
Страница 108: ...A Technical specifications and index A 4 Festo P BE DLP VSE en 0206a...