3. Installation
3-17
Festo P.BE-DLP-VSE-... en 0206a
3.3.3 Connecting the field bus
Field bus cable
Use a twisted screened 2-core cable for the field bus.
Please note
Please observe the cable specifications.
During the exchange of data, transmission errors, signal
reflections and signal attenuation occur, especially with
high baud rates. Both can lead to transmission faults. The
causes of reflections may be:
– missing or incorrect terminating resistor
– branches
The causes of signal attenuation may be:
– transmission over long distances
– unsuitable cables
Please refer to the manual for your controller for informa-
tion on the cable type to be used.
If you use the Festo IP65 plug, the cable must have a
diameter of 7-10 mm.
Please note
Connect the screening of the field bus cable with a short
cable to the earth potential (PE) (length of cable max.
20 cm, cross-sectional area at least 1.5 mm
2
)