4. Commissioning
4-21
Festo P.BE-DLP-VSE-... en 0206a
4.2.4 Operation with general DP master
The Festo Local control unit can be controlled from any PLC,
PC or industrial PC with a PROFIBUS-DP module in accord-
ance with EN 50170 (DIN 19245). Information on the func-
tions FREEZE, SYNC and the DP identifiers can be found in
section 4.2.1.
Bus run-up
Before the Local control unit can be commissioned properly,
the DP master must perform the following functions in the
sequence specified.
1. send parametrizing telegrams
2. send configuration telegrams
3. request diagnostic information
4. start cyclic data transmission
The structure and contents of the individual telegrams are
described in the following chapters.
Содержание DLP-VSE Series
Страница 1: ...Manual Local control unit DLP VSE DLP VSE DP DLP VSE ASI Manual 396 535 en 0206a...
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE DLP VSE en 0206a...
Страница 8: ...Contents and general instructions VI Festo P BE DLP VSE en 0206a...
Страница 20: ...1 Summary of components 1 8 Festo P BE DLP VSE en 0206a...
Страница 54: ...3 Installation 3 30 Festo P BE DLP VSE en 0206a...
Страница 84: ...4 Commissioning 4 30 Festo P BE DLP VSE en 0206a...
Страница 104: ...5 Diagnosis 5 20 Festo P BE DLP VSE en 0206a...
Страница 108: ...A Technical specifications and index A 4 Festo P BE DLP VSE en 0206a...