100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
User Guide
Page 287
8.4.2 CHANNEL CONFIGURATION DATA (Cont.)
CHANNEL 11
Notes
1. For maths, totalisers and counters, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value re-
turned will be the previously con
fi
gured constant value.
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Ch11 Span high
Upper span value (display full scale)
Scaled
Read only
06CF (1743)
1
Ch11 Span low
Lower span value (display ‘zero’)
Scaled
Read only
06D0 (1744)
1
Ch11 Zone high
Zone high value (two decimal places)
Scaled
Read only
06D1 (1745)
1
Ch11 Zone low
Zone low value (two decimal places)
Scaled
Read only
06D2 (1746)
1
Ch11 PV type
Input type
Enum
Read only
06D3 (1747)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Ch11 Decimal places
Number of decimal places (0 to 9)
Uint16
Read only
06D4 (1748)
1
(used by all scaled parameters except where stated)
Ch11 Colour
Channel colour (0 to 55) (See
Annex B
for de
fi
nitions)
Enum
Read only
06D5 (1749)
1
Ch11 Units
Units string (up to
fi
ve characters)
String_5
Read only
06D6 (1750)
3
Spare
06D9
(1753)
2
Ch11 Open string
Open Digital Input string (up to eight characters)
String_8
Read only
06DB (1755)
4
Spare
06DF
(1759)
4
Ch11 Close string
Closed Digital Input string (up to eight characters)
String_8
Read only
06E3 (1763)
4
Spare
06E7
(1767)
4
Ch11 Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only
06EB (1771)
10
Spare
06F5
(1781)
10
Ch11 No of alarms
Number of alarms on this channel (0 to 2)
Uint16
Read only
06FF (1791)
1
Ch11 PV format
Enum
Read only
0700 (1792)
1
0 = Numeric
1 = Digital strings
Spare
0701
(1793)
60
Ch11 Alarm 1 enable
Alarm 1 enable
Enum
Read only
073D (1853)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Ch11 Alarm 1 type
Alarm 1 type
Enum
Read only
073E (1854)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Ch11 Alarm 1 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 073F (1855)
1
Spare
0740
(1856)
10
Ch11 Alarm 2 enable
Alarm 2 enable (As alarm 1 enable, above)
Enum
Read only
074A (1866)
1
Ch11 Alarm 2 type
Alarm 2 type (As alarm 1 type, above)
Enum
Read only
074B (1867)
1
Ch11 Alarm 2 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 074C (1868)
1
Spare
074D
(1869)
10
Ch11 Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only
0757(1879)
1
Ch11 Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only
0758 (1880)
1
Ch11 Alarm 3 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0759 (1881)
1
Spare
075A
(1882)
10
Ch11 Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only
0764 (1892)
1
Ch11 Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only
0765 (1893)
1
Ch11 Alarm 4 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0766 (1894)
1
Spare
0767
(1895)
10