8 .4.3 Channel Run-Time data
These tables show addresses for channel input values for channels 1 to 12 inclusive.
Generally: channel N address = channel 1 a 3(N-1) (decimal). For channels 75 to 100 (EtherNet/IP
option only), see
table 4.3.21
.
CHANNEL 1
Ch1 value
Current process value (PV)
Scaled
See note
A1D9 (41433)
1
Ch1 status
Channel status
Enum
Read only
A1DA (41434)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Over
fl
ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Ch1 Alarms
Alarm information
Uint16
-
A1DB (41435)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare
CHANNEL 2
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Ch2 value
Current process value (PV)
Scaled
See note
A1DC (41436)
1
Ch2 status
Channel status
Enum
Read only
A1DD (41437)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Over
fl
ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Ch2 Alarms
Alarm information
Uint16
-
A1DE (41438)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare