100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
Page 130
4.3.12 (Cont.) TOTALISER MODBUS ADDRESSING
The following table gives addresses for totaliser 1 confi guration data. Generally: Totaliser N parameter
address = totaliser 1 parameter a 162 (N-1) (decimal).
For full details of the Modbus TCP implementation, see
section 8
.
TOTALISER CONFIGURATION DATA
TOTALISER 1
Note: A/B Switching:
B values are not accessible via modbus
for this software version. Span, Zone,
Colour etc. are therefore all setting A
Notes:
1. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
2. If more than 100 Maths channels are confi gured in ‘
Virtual channels
’, then the extra channels
occupy totaliser address space such that maths channel 101 occupies totaliser 1 address and so
on. Totaliser 1 value is to be found at the fi rst address after the fi nal maths channel. Thus, if there
are, for example, 105 maths channels, then Totaliser 1 is found where Totaliser 6 would normally
be. This in turn affects counter addressing as counter addresses immediately follow totaliser ad-
dresses, and in the above example, Counter 1 value would be found at counter 6 address.
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Span high
Upper span value (display full scale)
Scaled
Read only
6F39 (28473)
1
Span low
Lower span value (display ‘zero’)
Scaled
Read only
6F3A (28474)
1
Zone high
Zone high value (two decimal places)
Scaled
Read only
6F3B (28475)
1
Zone low
Zone low value (two decimal places)
Scaled
Read only
6F3C (28476)
1
PV type
Input type
Enum
Read only
6F3D (28477)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Decimal places
Number of decimal places (0 to 9)
Uint16
Read only
6F3E (28478)
1
(used by all scaled parameters except where stated)
Colour
Channel colour (0 to 55) (See
Annex B
for defi nitions)
Enum
Read only
6F3F (28479)
1
Units
Units string (up to fi ve characters)
String_5
Read only
6F40 (28480)
3
Spare
6F43
(28483)
2
Open string
Open Digital Input string (up to eight characters)
String_8
Read only
6F45 (28485)
4
Spare
6F49
(28489)
4
Close string
Closed Digital Input string (up to eight characters)
String_8
Read only
6F4D (28493)
4
Spare
6F51
(28497)
4
Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only
6F55 (28501)
10
Spare
6F5F
(28511)
10
No of alarms
Number of alarms on this channel
Uint16
Read only
6F69 (28521)
1
PV format
Enum
Read only
6F6A (28522)
1
0 = Numeric
1 = Digital strings
Spare
6F6B
(28523)
60
Alarm 1 enable
Alarm 1 enable
Enum
Read only
6FA7 (28583)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Alarm 1 type
Alarm 1 type
Enum
Read only
6FA8 (28584)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Alarm 1 setpoint
Trigger setpoint (see note)
Scaled
Read/Write 6FA9 (28585)
1
Spare
6FAA
(28586)
10
Alarm 2 enable
Alarm 2 enable (As alarm 1 enable above)
Enum
Read only
6FB4 (28596)
1
Alarm 2 type
Alarm 2 type (As alarm 1 type above)
Enum
Read only
6FB5 (28597)
1
Alarm 2 setpoint
Trigger setpoint (see note 1)
Scaled
Read/Write 6FB6 (28598)
1
Spare
6FB7
(28599)
10
Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only
6FC1 (28609)
1
Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only
6FC2 (28610)
1
Alarm 3 setpoint
Trigger setpoint (see note 1)
Scaled
Read/Write 6FC3 (28611)
1
Spare
6FC4
(28612)
10
Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only
6FCE (28622)
1
Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only
6FCF (28623)
1
Alarm 4 setpoint
Trigger setpoint (see n ote 1)
Scaled
Read/Write 6FD0 (28624)
1
Spare
6FD1
(28625)
10