MASTER COMMS CHANNEL CONFIGURATION EXAMPLE
This example describes a recorder (Furn1 Master) acting as a master to two other recorders (Furn1 Record
and Furn2 Record) and a controller (Furn1 Control). This example shows only the confi guration pages nec-
essary to set up the master input/output channels and the slave Comms channel. It is assumed that:
a. the master comms confi guration has been completed with Remote devices 1, 2 and 3 set up as Furn1
Control, Furn1 Record and Furn2 control, respectively.
b. all recorders are of the type described in this manual. Other types of slave may need more inputs, or
different inputs to be entered.
EXAMPLE (see fi gure 4.3.16j)
to:
Read Loop1 PV from Controller 1 to Channel 1 of Recorder 1 (the master)
Read Channel 1 from Recorder 2 to Channel 2 of the master
Write Channel 2 of the Master to Channel 1 of Recorder 3.
Controller 1
(Slave 1)
Furn1 Control
Furn1 PV1
Recorder 3
(Slave 3)
Furn2 Record
Channel 1
Recorder 2
(Slave 2)
Furn1 Record
Furn1 Temp1
Recorder 1
(Master)
Furn1Master
Channel 1
Channel 2
Channel 2
Figure 4.3.16j Required setup