100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
User Guide
Page 306
8.4.7 IEEE 32-BIT CHANNEL CONFIGURATION DATA (Cont.)
CHANNEL 7
Notes
1. For
maths
,
totalisers
and
counters
, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value re-
turned will be the previously con
fi
gured constant value.
Ch7 span high
Upper span value (display full scale)
Float
Read only
D5BF (54719)
2
Ch7 span low
Lower span value (display ‘zero’)
Float
Read only
D5C1 (54721)
2
Ch7 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D5C3 (54723)
2
Ch7 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D5C5 (54725)
2
Ch7 Alarm 1 setpoint
Trigger setpoint for alarm 1 (Note 2)
Float
Read/Write D5C7 (54727)
2
Ch7 Alarm 2 setpoint
Trigger setpoint for alarm 2 (Note 2)
Float
Read/Write D5C9 (54729)
2
Ch7 Alarm 3 setpoint
Trigger setpoint for alarm 3 (Note 2)
Float
Read/Write D5CB (54731)
2
Ch7 Alarm 4 setpoint
Trigger setpoint for alarm 4 (Note 2)
Float
Read/Write D5CD (54733)
2
Spare
D5CF
(54735)
20
CHANNEL 8
Ch8 span high
Upper span value (display full scale)
Float
Read only
D5E3 (54755)
2
Ch8 span low
Lower span value (display ‘zero’)
Float
Read only
D5E5 (54757)
2
Ch8 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D5E7 (54759)
2
Ch8 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D5E9 (54761)
2
Ch8 Alarm 1 setpoint
Trigger setpoint for alarm 1 (Note 2)
Float
Read/Write D5EB (54763)
2
Ch8 Alarm 2 setpoint
Trigger setpoint for alarm 2 (Note 2)
Float
Read/Write D5ED (54765)
2
Ch8 Alarm 3 setpoint
Trigger setpoint for alarm 3 (Note 2)
Float
Read/Write D5EF (54767)
2
Ch8 Alarm 4 setpoint
Trigger setpoint for alarm 4 (Note 2)
Float
Read/Write D5F1 (54769)
2
Spare
D5F3
(54771)
20
CHANNEL 9
Ch9 span high
Upper span value (display full scale)
Float
Read only
D607 (54791)
2
Ch9 span low
Lower span value (display ‘zero’)
Float
Read only
D609 (54793)
2
Ch9 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D60B (54795)
2
Ch9 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D60D (54797)
2
Ch9 Alarm 1 setpoint
Trigger setpoint for alarm 1 (Note 2)
Float
Read/Write D60F (54799)
2
Ch9 Alarm 2 setpoint
Trigger setpoint for alarm 2 (Note 2)
Float
Read/Write D611 (54801)
2
Ch9 Alarm 3 setpoint
Trigger setpoint for alarm 3 (Note 2)
Float
Read/Write D613 (54803)
2
Ch9 Alarm 4 setpoint
Trigger setpoint for alarm 4 (Note 2)
Float
Read/Write D615 (54805)
2
Spare
D617
(54807)
20
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length