100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
Page 161
4.3.16 MASTER COMMS (Cont.)
MASTER OUTPUT 1 SETUP
This shows the setup required in order to output the master’s channel 2 (Furn1 Temp1) to Furn2 Record
channel 1. The Descriptor Furn1 Temp1 has been entered as the Output Name. This happens to be the
same as the channel descriptor, but could be any required text string.
Output Channel Number
Enable
Output Type
Slave
Parameter
Point Type
Point Number
Process Value
Descriptor
Source
Default
On Error Write Default
1) Furn1 Temp 1
Discard
Apply
Master Comms
3) Furn2 Record
Comms Channel
Channel
Medium Priority
2) Furn1 Temp1
0
1
Furn1 PV1
Channel Number
Value
Input Type
Scale Low
Scale High
Unadjusted
0
1000
1) Furn1 Temp1
658.3654
Slave Comms
Deg C
Deg C
Units
Deg C
Scale Type
Linear
Scale Divisions - Major
Scale Divisions Minor
10
1
Descriptor
Furn1 Temp 1
A/B Switching
Discard
Apply
Figure 4.3.16m Master Output 1 setup example
SLAVE INPUT CHANNEL 1 SETUP
Figure 4.3.16n shows how to set up a slave channel to read an input from a master. Note that the scaling
of this channel must match th e scaling of the source channel.
Figure 4.3.16n Slave channel setup