100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
Page 82
HA029324
Issue 11 Oct 14
4.3.6 Event confi guration
A number of internal and triggers are available for use in initiating Events which will then run job lists.
Events can have up to two sources each, but can themselves be used as sources allowing a large number
of inputs to be used. Input sources can be logically combined, and can be inverted if required.
Apply
Discard
Select 1 to 96
Event Number
1) Event 1
Event 1
1
No Action
Alarm on Group
1) Group 1
Point Alarm
Math 12
2
Source 1
And
Not Source 2
Source 1
Descriptor
Select job number
Job Number
Category
Select Job Category
Select source 1
On Group
Source 2
Select source 2
On
Alarm
Source 1 Sense
Operator
Source 2 Sense
Make sub-sub selection (if any)
Select logic combination: Only, AND,
OR, NAND, NOR, XOR.
Select source inversion or not
Select source inversion or not
Make source 1 sub selection (if any)
Make source 2 sub selection (if any)
Figure 4.3.6 Event confi guration menu layout (typical)
EVENT NUMBER
Allows the required event (1 to 96) to be selected for confi guration.
SOURCE TYPES
Note: Event sources associated with options appear only if those options are fi tted.
Off
The event is disabled
Global alarm
The event is active whilst any one or more alarms is active.
Global Unack’d alarm
The event is active as long as there is an unacknowledged alarm present.
Comms channel timeout The event is set if no communication has been made with ‘Comms’ channels
within the Comms channel timeout period set in Instrument confi guration (
sec-
tion 4.3.1
). The source is reset when the next communication occurs.
Timer active
The event is triggered when a specifi ed timer (
section 4.3.14
) becomes active.
Batch Running*
The event is triggered when a batch is started and remains active until the
batch stops. If Scope = ‘Group’ in Batch confi guration (
section 4.3.10
) then a
group can be specifi ed. If Scope = ‘Instrument’, the group select fi eld does not
appear. If the Batch option is not fi tted, ‘Batch running’ does not appear in the
picklist.
Batch Start*
The event is triggered, fl eetingly, when a batch is started If Scope = ‘Group’ in
Batch confi guration (
section 4.3.10
) then a group can be specifi ed. If Scope =
‘Instrument’, the group select fi eld does not appear. If the Batch option is not
fi tted, ‘Batch running’ does not appear in the picklist.
Event
Allows another event to be specifi ed as a source.
Point alarm
Triggered by the specifi ed alarm on the specifi ed point.
Unack’d point alarm
Triggered by the specifi ed alarm on the specifi ed point. Remains active until
the alarm is acknowledged (
section 3.1.4
).
Alarm on Group
Triggered if any alarm in the specifi ed group becomes active.
(Continued)
* Batch stop also available - see below.