4.3.21 ETHERNET/IP OPTION (Cont.)
CONFIGURATION
Figure 4.3.21a shows the confi guration page.
Figure 4.3.21a Ethernet/IP option confi guration (large frame unit)
Import Table
Touching this fi eld opens the fi le window, allowing the user to select a .uht fi le for im-
port. This fi le may be a fi le previously exported using the ‘Export table’ fi eld, in which
case it will be found in the \user\ folder, or it may be located on a USB stick or other
memory device, in which case it will appear in a separate folder.
Export Table
This allows the user to export the current table to the instrument’s fl ash memory or to
a memory stick or other memory device. Exported tables may be imported into other
suitable instruments, or into a pc to be used as a ‘template’ for creating other tables.
Status
Initialising: Initial status at start-up. Switches to ‘Online’ when the Ethernet/IP con-
fi guration has been read successfully and the server has completed its
confi guration.
Online:
All cyclic inputs and outputs are updated continuously
Offl ine:
The server ignores all transactions and tables are not updated.
I/O Table
Select ‘Inputs’ (Server -->Client) or ‘Outputs’ (Client --> Server) for the displayed table.
Input ( output) 1
Shows the fi rst selected input (output) parameter which is to be read or written. Input
tables can be completed by importing a suitable previously confi gured table, by en-
tering individual parameters into each fi eld, by using the Wizard key or by using the
Default table and editing it as necessary. See ‘Table entry’, ‘Wizard key’ and/or ‘De-
fault table’, below for further details. Output tables cannot be edited
Input (output) 2 to 200
As for input (output) 1, above, but for the remaining table entries.
Apply key
Touch this to save the table confi guration. An error message is generated if the chan-
nel number is out of range, or if the syntax is incorrect. See ‘Table entry’, below.
Discard key
Touching this key causes all changes made since the previous ‘Apply’ to be discarded.
Wizard key
This provides a mechanism for the rapid entry of input and output table parameters.
See ‘
WIZARD
’ below for a fuller explanation.
Default Table key
Fills the displayed input or output table with channel and math PV parameters. This
can then be edited either on an entry by entry basis, or by exporting the table so that
it may be edited in a pc. Described in more detail
later
.
Show Errors key
Shows any errors in the current confi guration. For each parameter without error, the
parameter’s Modbus address is displayed instead.
Import Table
Export Table
Status
I/O Table
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 200
eiptable
eiptable
Online
Inputs
Server - - > Client
Channel.1.pv
Channel.2.pv
Channel.3.pv
Channel.4.pv
Channel.5.pv
Ch
Apply
Discard
Wizard
Default Table