SYSTEM PARAMETER
Proline t-mass 65 MODBUS RS485
46
Hauser
15
SYSTEM PARAMETER
Function description, SYSTEM PARAMETER group
POSITIVE ZERO RETURN
Description
Use this function to interrupt evaluation of measured variables. For example, the
output signal should be set to zero flow during operations such as pipe cleaning
The setting acts on all functions and outputs of the measuring device.
If the positive zero return is active, the notice message #601 "POSITIVE ZERO-
RET" is displayed.
If the status input is appropriately configured, the positive zero return function
can also be activated by using the status input (ASSIGN STATUS INPUT
31).
Options
0 = OFF
1 = ON (signal output is set to zero flow value, temperature is as normal)
Factory setting
OFF
MODBUS register:
Data type:
Access:
5503
Integer
read/write
FLOW DAMPING
Description
Use this function to enter a value for damping the measured flow and
temperature signals. The sensitivity of the flow measurement signal can be
reduced with respect to transient flows and interference peaks.
The damping acts prior to other damping functions (e. g. display, time constant).
User input
0 to 100 s
Factory setting
1 s
MODBUS register:
Data type:
Access:
5510
Float
read/write