Function description, STATUS INPUT group
ASSIGN STATUS INPUT
Description
Use this function to assign a switching function to the status input.
• Positive zero return is active as long as the level is present at the status input
(continuous signal). All other assignments react to a change in level (pulse) at
the status input.
• If you select OFF, the only function shown in this function group is the
Options
0 = OFF
1 = RESET TOTALIZER 1
2 = POSITIVE ZERO RETURN
3 = ZERO POINT ADJUST
4 = RESET TOTALIZER 2
5 = RESET ALL TOTALIZERS
6 = GAS GROUP
Factory setting
OFF
MODBUS register:
Data type:
Access:
4301
Integer
read/write
ACTIVE LEVEL
Description
Use this function to define whether the assigned switching function (see
ASSIGN STATUS INPUT function) is triggered or sustained when the signal
level is present (HIGH) or not present (LOW).
Options
0 = LOW
1 = HIGH
Factory setting
HIGH
MODBUS register:
Data type:
Access:
4302
Integer
read/write
MINIMUM PULSE WIDTH
Description
Use this function to specify the minimum pulse width which the input pulse has
to reach in order to trigger the selected switching function (ASSIGN STATUS
INPUT function).
Options
20 to 100 ms
Factory setting
50 ms
MODBUS register:
Data type:
Access:
4303
Float
read/write
ACTUAL STATUS INPUT
Description
Use this function to view the current level of the status input.
Display
0 = LOW
1 = HIGH
MODBUS register:
Data type:
Access:
4305
Integer
read