HEAT FLOW
Proline t-mass 65 MODBUS RS485
44
Hauser
14
HEAT FLOW
Function description, HEAT FLOW group
CALORIFIC VALUE TYPE
Description
Use this function to select the measured variable on which the combustion
value is based.
Options
0 = MASS
1 = CORRECTED VOLUME
Factory setting
MASS
MODBUS register:
Data type:
Access:
9977
Integer
read/write
MODE 1
Description
Use this function to select a mode for calculating the heat flow (GAS GROUP 1).
Options
0 = AUTO NET
1 = AUTO GROSS
2 = MANUAL
Factory setting
AUTO NET
MODBUS register:
Data type:
Access:
9973
Integer
read/write
HEATING VALUE 1
Prerequisite
This function is
only
available if MANUAL was selected in the MODE 1
function (
44).
Description
Use this function to enter a user-specific calorific value.
Input/display
5-digit floating-point number
Factory setting
0.0
The corresponding unit is taken from the UNIT CALORIFIC VALUE MASS
(
8) or UNIT CALORIFIC VALUE CORRECTED VOLUME function
MODBUS register:
Data type:
Access:
9975
Float
read/write
MODE 2
Description
Use this function to select a mode for calculating the heat flow (GAS GROUP 2).
Options
0 = AUTO NET
1 = AUTO GROSS
2 = MANUAL
Factory setting
AUTO NET
MODBUS register:
Data type:
Access:
9974
Integer
read/write
HEATING VALUE 2
Prerequisite
This function is
only
available if MANUAL was selected in the MODE 2
function (
44).
Description
Use this function to enter a user-specific calorific value.
Input/display
5-digit floating-point number
Factory setting
0.0
The corresponding unit is taken from the UNIT CALORIFIC VALUE MASS
(
8) or UNIT CALORIFIC VALUE CORRECTED VOLUME function
MODBUS register:
Data type:
Access:
9978
Float
read/write