GAS
Proline t-mass 65 MODBUS RS485
42
Hauser
GAS TYPE 2 to 8
Prerequisite
The number of functions available here is dependent upon the setting in the
function NUMBER OF GASES (
40).
Description
Use this function to select the gas type.
Options
0 = AIR
1 = AMMONIA
2 = ARGON
3 = BUTANE
4 = CARBON DIOXIDE
5 = CARBON MONOXIDE
6 = CHLORINE
7 = ETHANE
8 = ETHYLENE
9 = HELIUM 4
10 = HYDROGEN NORMAL
11 = HYDROGEN CHLORIDE
12 = HYDROGEN SULFIDE
13 = KRYPTON
14 = METHANE
15 = NEON
16 = NITROGEN
17 = OXYGEN
18 = PROPANE
20 = XENON
22 = NOT USED
Factory setting
NOT USED
MODBUS register:
GAS TYPE 2
GAS TYPE 3
GAS TYPE 4
GAS TYPE 5
GAS TYPE 6
GAS TYPE 7
GAS TYPE 8
Data type:
Access:
9722
9725
9728
9731
9734
9737
9740
Integer
read/write
MOLE % GAS 2 to 8
Prerequisite
The number of functions available here is dependent upon the setting in the
function NUMBER OF GASES (
40).
Description
Use this function to enter the Mole % of the GAS TYPE 2 to 8.
User input
000.00 % to 100.00 %
Factory setting
000.00 %
MODBUS register:
MOLE-% GAS 2
MOLE-% GAS 3
MOLE-% GAS 4
MOLE-% GAS 5
MOLE-% GAS 6
MOLE-% GAS 7
MOLE-% GAS 8
Data type:
Access:
9723
9726
9729
9732
9735
9738
9741
Float
read/write
CHECK VALUES
Prerequisite
This function is only available if there is an error in the Mole % values.
Description
The error message MIXTURE NOT 100% appears if the entered values do not
add up to 100%. The entries have to be checked and corrected before the gas
group can be saved and used for flow measurement (see option YES
function
43).
Display
0 = OK (only via MODBUS communication)
1 = MIXTURE NOT 100%
2 = MIXTURE ERROR (only via MODBUS communication)
MODBUS register:
Data type:
Access:
9763
Integer
read/write
Function description, GAS group